Notifications
You must be signed in to change notification settings - Fork 952
Commit
This commit does not belong to any branch on this repository, and may belong to a fork outside of the repository.
OCP power shelves by Delta and LiteOn (#1437)
* wip * more details * remove header comments * fix module ports * use description instead of comment + caps part num * reorg fields, add missing info, remove description * fix delta models * fix 1000base-t * remove slug from module * remove airflow, depth, height from module * change PSUs from devices to modules * add detailed info for liteon psu * remove trailing spaces * new line at end of file * use mgmt instead of console --------- Co-authored-by: Daniel W. Anner <[email protected]>
- Loading branch information
1 parent
b292c04
commit e66fc0a
Showing
8 changed files
with
338 additions
and
0 deletions.
There are no files selected for viewing
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,34 @@ | ||
--- | ||
manufacturer: Delta | ||
model: AD-208/24C-A | ||
slug: delta-ad-208-24c-a | ||
part_number: AD-208/24C-A | ||
u_height: 0 | ||
is_full_depth: false | ||
airflow: passive | ||
comments: | | ||
Open Compute Project ORv2 Top of Rack Surge PDU | ||
V2 AC Power Distribution Unit | ||
INPUT: 208V~,3W+PE, 50-60HZ,24A MAX (x2) | ||
OUTPUT: 208V~,3W+PE, 50-60HZ,24A MAX (x2) | ||
FB PN: 07-000866 | ||
power-ports: | ||
- name: ac-input-1 | ||
label: TOP POWER SHELF | ||
type: nema-l21-30p | ||
- name: ac-input-2 | ||
label: BOTTOM POWER SHELF | ||
type: nema-l21-30p | ||
power-outlets: | ||
- name: ac-output-1 | ||
label: TOP POWER SHELF | ||
type: other | ||
power_port: ac-input-1 | ||
- name: ac-output-2 | ||
label: BOTTOM POWER SHELF | ||
type: other | ||
power_port: ac-input-2 |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,34 @@ | ||
--- | ||
manufacturer: Delta | ||
model: AD-208/24C-B | ||
slug: delta-ad-208-24c-b | ||
part_number: AD-208/24C-B | ||
u_height: 0 | ||
is_full_depth: false | ||
airflow: passive | ||
comments: | | ||
Open Compute Project ORv2 Top of Rack Surge PDU | ||
V2 AC Power Distribution Unit | ||
INPUT: 208V~,3W+PE, 50-60HZ,24A MAX (x2) | ||
OUTPUT: 208V~,3W+PE, 50-60HZ,24A MAX (x2) | ||
FB PN: 07-000866 | ||
power-ports: | ||
- name: ac-input-1 | ||
label: TOP POWER SHELF | ||
type: nema-l21-30p | ||
- name: ac-input-2 | ||
label: BOTTOM POWER SHELF | ||
type: nema-l21-30p | ||
power-outlets: | ||
- name: ac-output-1 | ||
label: TOP POWER SHELF | ||
type: other | ||
power_port: ac-input-1 | ||
- name: ac-output-2 | ||
label: BOTTOM POWER SHELF | ||
type: other | ||
power_port: ac-input-2 |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,68 @@ | ||
--- | ||
manufacturer: Delta | ||
model: SG-11M-A | ||
slug: delta-sg-11m-a | ||
part_number: SG-11M-A | ||
u_height: 3 | ||
is_full_depth: true | ||
airflow: front-to-rear | ||
comments: | | ||
Open Compute Project ORv2 compatible Power Shelf | ||
Fits 21" ORv2 racks only | ||
FB PN: 14-000071 | ||
Takes PSU type DPST-2130CB-A | ||
power-ports: | ||
- name: ac-input-a | ||
label: AC INPUT A | ||
type: other | ||
- name: ac-input-b | ||
label: AC INPUT B | ||
type: other | ||
power-outlets: | ||
- name: ac-output-a1 | ||
type: iec-60320-c13 | ||
power_port: ac-input-a | ||
feed_leg: A | ||
- name: ac-output-a2 | ||
type: iec-60320-c13 | ||
power_port: ac-input-a | ||
feed_leg: B | ||
- name: ac-output-a3 | ||
type: iec-60320-c13 | ||
power_port: ac-input-a | ||
feed_leg: C | ||
- name: ac-output-b1 | ||
type: iec-60320-c13 | ||
power_port: ac-input-b | ||
feed_leg: A | ||
- name: ac-output-b2 | ||
type: iec-60320-c13 | ||
power_port: ac-input-b | ||
feed_leg: B | ||
- name: ac-output-b3 | ||
type: iec-60320-c13 | ||
power_port: ac-input-b | ||
feed_leg: C | ||
- name: dc-output-bus | ||
type: dc-terminal | ||
interfaces: | ||
- name: Management | ||
label: MGMT | ||
type: 1000base-t | ||
mgmt_only: true | ||
module-bays: # has a bay for some kind of COMM card but I have no details about it | ||
- name: psu-1a | ||
label: 1A | ||
- name: psu-2a | ||
label: 2A | ||
- name: psu-3a | ||
label: 3A | ||
- name: psu-1b | ||
label: 1B | ||
- name: psu-2b | ||
label: 2B | ||
- name: psu-3b | ||
label: 3B |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,50 @@ | ||
--- | ||
manufacturer: Delta | ||
model: SG110-A | ||
slug: delta-sg110-a | ||
part_number: SG110-A | ||
u_height: 3 | ||
is_full_depth: true | ||
airflow: front-to-rear | ||
comments: | | ||
Open Compute Project ORv1/v2 compatible Power Shelf | ||
Stingray v1 | ||
Fits 21" ORv1/v2 racks and 19" EIA racks (with proper adapters) | ||
Can take up to 6 PSU. In configurations where only 4 PSU are used, slots 1A and 3B are covered / unused. | ||
Takes PSU type DPST-2130CB-A | ||
power-ports: | ||
- name: ac-input-a | ||
label: AC INPUT A | ||
type: other | ||
- name: ac-input-b | ||
label: AC INPUT B | ||
type: other | ||
power-outlets: | ||
- name: dc-output-bus-left | ||
type: dc-terminal | ||
- name: dc-output-bus-center | ||
type: dc-terminal | ||
- name: dc-output-bus-right | ||
type: dc-terminal | ||
interfaces: | ||
- name: Management | ||
label: RJ45 | ||
type: 1000base-t | ||
mgmt_only: true | ||
module-bays: | ||
- name: psu-1a | ||
label: 1A | ||
- name: psu-2a | ||
label: 2A | ||
- name: psu-3a | ||
label: 3A | ||
- name: psu-1b | ||
label: 1B | ||
- name: psu-2b | ||
label: 2B | ||
- name: psu-3b | ||
label: 3B |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,85 @@ | ||
--- | ||
manufacturer: LiteOn | ||
model: PF-2273-2L1M-LF | ||
slug: liteon-pf-2273-2l1m-lf | ||
part_number: PF-2273-2L1M-LF | ||
u_height: 3 | ||
is_full_depth: true | ||
airflow: front-to-rear | ||
comments: | | ||
Open Compute Project ORv1/v2 compatible Power Shelf | ||
* 3-phase, 5-wire 220 / 230 / 240VAC | ||
* 27kW power output (3kW x 9; 12.5VDC/2160A) | ||
* 3OU shelf accepts up to 10 hot-swappable 3kW Power Supply Units for 9+1 redundant operation | ||
* 21-inch shelf with a height of 3 OU (OpenU), 5.11 inches (130 mm) | ||
* Communication with Li-ion Battery Backup Shelf (BBS) | ||
* Real-time PSU and BBS monitoring and control | ||
* Remote control PSU On/Off through the optional Shelf Controller | ||
* Supports 3 sets of bus bars to deliver DC power to load | ||
* Supports 6x C13 outlets for external AC load | ||
Fits 21" ORv1/v2 racks only | ||
Takes PSU type PSU-PS-2302-1L1U-LF | ||
weight: 27 | ||
weight_unit: kg | ||
power-ports: | ||
- name: ac-input-a | ||
type: other | ||
- name: ac-input-b | ||
type: other | ||
power-outlets: | ||
- name: ac-output-a1 | ||
type: iec-60320-c13 | ||
power_port: ac-input-a | ||
feed_leg: A | ||
- name: ac-output-a2 | ||
type: iec-60320-c13 | ||
power_port: ac-input-a | ||
feed_leg: B | ||
- name: ac-output-a3 | ||
type: iec-60320-c13 | ||
power_port: ac-input-a | ||
feed_leg: C | ||
- name: ac-output-b1 | ||
type: iec-60320-c13 | ||
power_port: ac-input-b | ||
feed_leg: A | ||
- name: ac-output-b2 | ||
type: iec-60320-c13 | ||
power_port: ac-input-b | ||
feed_leg: B | ||
- name: ac-output-b3 | ||
type: iec-60320-c13 | ||
power_port: ac-input-b | ||
feed_leg: C | ||
- name: dc-output-bus-left | ||
type: dc-terminal | ||
- name: dc-output-bus-center | ||
type: dc-terminal | ||
- name: dc-output-bus-right | ||
type: dc-terminal | ||
module-bays: | ||
- name: psc | ||
description: Power Shelf Controller | ||
- name: psu-01 | ||
label: N+1 R | ||
- name: psu-02 | ||
label: S | ||
- name: psu-03 | ||
label: T | ||
- name: psu-04 | ||
label: R | ||
- name: psu-05 | ||
label: S | ||
- name: psu-06 | ||
label: T | ||
- name: psu-07 | ||
label: R | ||
- name: psu-08 | ||
label: S | ||
- name: psu-09 | ||
label: T | ||
- name: psu-10 | ||
label: R |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,12 @@ | ||
--- | ||
manufacturer: Delta | ||
model: DPST-2130CB-A | ||
part_number: DPST-2130CB-A | ||
comments: | | ||
Switching Power Supply | ||
Stingray Power Supply | ||
12.5V/168A/2130W | ||
FB PN: 03-000261 |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,34 @@ | ||
--- | ||
manufacturer: LiteOn | ||
model: CM-12CP-010U | ||
part_number: CM-12CP-010U | ||
weight: 1.59 | ||
weight_unit: lb | ||
comments: | | ||
LiteOn Power Shelf Controller | ||
* Monitors up to 10 PSUs and 8 BBUs | ||
* Hot-swappable for easy installation and maintenance | ||
* Configurable alarm and reminder notifications | ||
* Real-time monitoring capabilities for power shelves and battery backup system | ||
* Real-time alarm logging and delivery | ||
* SNMP (v2c, v3), Web server, RestAPI, and IPMI support for remote management | ||
* Secure web interface | ||
* Efficiency management system for optimizing power shelf efficiency | ||
* 10/100/1000 Ethernet port support IPv6, SNMPv3 | ||
* CAN communication port | ||
console-ports: | ||
- name: serial | ||
label: SERVICE | ||
type: de-9 | ||
- name: can-1a | ||
label: CAN-1A | ||
type: rj-45 | ||
- name: can-1b | ||
label: CAN-1B | ||
type: rj-45 | ||
interfaces: | ||
- name: mgmt | ||
label: LAN | ||
type: 1000base-t | ||
mgmt_only: true |
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
Original file line number | Diff line number | Diff line change |
---|---|---|
@@ -0,0 +1,21 @@ | ||
--- | ||
manufacturer: LiteOn | ||
model: PSU-PS-2302-1L1U-LF | ||
part_number: PSU-PS-2302-1L1U-LF | ||
weight: 2.5 | ||
weight_unit: kg | ||
comments: | | ||
The 3KW Power Supply Unit (PSU) efficiently supplies both main output DC power and standby DC | ||
power from either AC or DC sources. This compact PSU provides 3kW, 12.5V / 240A for main power | ||
output and 30W, 12V / 2.5A for standby power applications. In addition, this PSU supports | ||
PMBUS1.2 with boot loader, LED status indicators, and circuit protection features. | ||
* 3kW, 12.5V / 240A main output power | ||
* 30W, 12V / 2.5A standby output power | ||
* Single-phase AC input and DC input | ||
* Interleaved Power Factor Correction (PFC) technique | ||
* High density design (30W / inch^3) | ||
* Platinum-rated efficiency | ||
* Parallel operation for capacity or redundancy | ||
* 16 unique PSU addresses | ||
* PMBUS1.2 communication protocol |